我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
MiCOM P343 - Differential & bias current measurement missing
Issue
In one of our installed MICOM P343 relay, Generator low impedance differential protection is enabled and protection is working fine however the differential & bias current measurement is not showing up in MEASUREMENT 3 folder. As per manual it should be available in Measurement 3 folder.

_____________________________________________________________

Product Line
MiCOM P343 Firmware version 35

_____________________________________________________________

Environment
Parameter "System config" [09.0B] value is set as invisible.

_____________________________________________________________
Solution
Issue can be resolved by either making visible the "System config" parameter or by upgrading the device to FW version 36. There is no harm in keeping the "System config" as invisible.

To upgrade the device please reach to local SE contact.
_____________________________________________________________

*Warning:  Installation, maintenance, up-gradation, down-gradation of MiCOM device should only be performed by qualified, competent personnel that have appropriate training and experience. Failure to follow the instructions / warnings in the Installation / Operation Guide can result in unwanted disruption to the power system, permanent damage to the device, severe injury or death.*

施耐德電機Taiwan

探索更多
產品:
探索更多
產品:

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings