{}
搜尋常見問題
Initial values from a converted Concept application does not get transferred to the PLC.
The reason this occurs is due to the checkbox for 'Initialize %MWi' not being selected in the CPU configuration.

To resolve the issue:
  • Open the CPU configuration window.
  • Select the checkbox 'Initialize %MWi'.
  • Rebuild the application.
  • Retest.

image.png

施耐德電機Taiwan

探索更多
系列:
可能有幫助的文章
探索更多
系列: