Why an Error popup ‘The run time is in use’ is displayed with EcoStruxure™ Operator Terminal Expert using HMIG5U22?

With the HMIG5U22, if a user wants to display the Runtime of the EcoStruxure™ Operator Terminal Expert project, it can occur that an error popup is displayed with the following message ‘the run time is in use’ but there is no real other runtime already running and the runtime never starts.

The root cause is:
The Runtime is tried to boot twice at startup by each way:
  1. By registry entry [HKEY_LOCAL_MACHINE\SOFTWARE\Microsoft\Windows\CurrentVersion\Run]
Note: To install the EOTE Runtime by the Installer creates this faulty registry entry.
2- By AppAutoStarter
Then Runtime detect the duplicate launch and shows the dialog "The Runtime is in use".

Hardware:  This issue is visible on HMIG5U22 running a Windows 10 LTSC operating system.

Software: EcoStruxure™ Operator Terminal Expert 3.2 SP1, SP2
Operating system: Windows 10 LTSC
Language: English, other languages can be concerned


Resolution:
This issue will be fixed in the next EcoStruxure™ Operator Terminal Expert version: V4.0.


Before this V4.0 version availability, you can apply this workaround:
To Remove the registry entry
  • In Windows menu, enter Regedit then browse to:
[HKEY_LOCAL_MACHINE\SOFTWARE\Microsoft\Windows\CurrentVersion\Run]
  • Delete:
"RTPrimaryBoot"="C:\\Program Files\\Schneider Electric\\Vijeo XD Runtime\\RTPrimaryBoot\\RTPrimaryBoot.exe"


施耐德電機Taiwan

探索更多
產品:
探索更多
產品:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings