我们今天能为您提供什么帮助?

Smart-UPS RT External Battery Pack Number Assignment

Issue: External battery packs connected to SRT or SRTL UPS models may be assigned a number that does not correspond to the order in which the battery pack is connected to the UPS.

Product Line: UPS models with SRT and SRTL prefix
Note: This does not apply to SRTL3KRM1UC UPS models, or UPS models with SRTG prefix

Environment: All models, all serial numbers; when multiple external battery packs are connected to the UPS

Cause: The battery packs will keep their initial number assignment even after disconnecting and reconnecting, regardless of UPS braindead.

Refer to the the following use case scenarios depending on whether the battery pack that is connected is new or not.

1. If a new battery pack that has not been connected to a UPS previously is connected to the UPS:

  • If the UPS is turned on, and the first battery pack is connected - it will be assigned number#1
  • If a 2nd fresh battery pack is connected - it will be assigned number#2
  • If the UPS is turned off, and multiple battery packs are connected to the UPS before the UPS is turned on, the battery packs may be assigned a sequence that may not correspond to the order in which they are physically connected.

2. If a battery pack that has previously been connected to a UPS, is now reconnected to a UPS:

  • The battery pack will keep its previously assigned number, unless this number is already assigned to a different battery pack that is connected to the UPS
  • If the initial number of the battery pack is already assigned to a different battery pack connected to the UPS, the battery pack will be assigned the next available number
Refer to the attached diagram for more information on the battery pack number assignment.

Note: After a UPS Firmware upgrade, the numbers assigned to the battery packs connected to the UPS may change. This is expected behavior and does not impact the functionality of the UPS or the battery packs.

Resolution:

It is recommended that the UPS be turned ON before any battery packs are connected, and after that to connect new battery packs one by one: allow each battery pack to be detected and assigned a number before connecting the next battery pack. When a battery pack is connected, it may perform an automatic firmware upgrade. The battery pack firmware upgrade needs to be allowed to complete before connecting the next battery pack. This will ensure that the battery pack sequence will correspond to the physical order in which they are connected.

施耐德電機Taiwan

附件
battery pack numbering flow chart.pdf [86.53 KB]
探索更多
系列:
探索更多
系列:

需要協助?

需要協助?

產品選型工具

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

支援中心

在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings