我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Adding a second BMENOP300 to the rack results in the power consumption to be exceeded for the BMXCPS3500.

Adding a second BMENOP0300 module to an existing rack that contains a BMENOC03xx module (i.e., BMENOC0311, etc.) with three other IO modules will result in the power consumption being exceeded for a BMXCPS3500 power supply.


i.e.,

rack




The issue occurred as a result of Control Expert basing the power consumption for the BMENOC03xx modules on the most restrictive value of 1.8A for the old hardware version (<=PV14).. as shown in the Control Expert  help.

The total consumption for the BMENOC311 and the two BMENOP0300 added to the rack results in a value of 4.922A.  This exceeded the limit of 4.5A for a BMXCPS3500.

pwr


The newer hardware version (>PV14), uses 0.9A as shown in the help. If the user is certain that the PV version for the BMENOC03xx module is greater than 14, A value of 1.8A can be subtracted from the value shown in the power supply bar graph (in red) and a value of add 0.9A can then be added to the resulting sum. The new power consumption value would then be 4.022A.  Otherwise, it is recommended to use a larger sized power supply (i.e.,'BMXCPS4002).


The following is from the Control Expert help:

help

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings