我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
SchneiderElectric_KBA_Basic_Meter_PM55xx Russian Language files issue

SchneiderElectric_KBA_Basic_Meter_PM55xx Russian Language files issue

Problem statement :

Pm5560 Meter set to Russian language, the Panel data is not visible and some of data labels are not visible in different screen navigations.
Russian Language issue

Causes identified :

  • This data label missing or data is missing in PM55xx when the Meter is set to the Russian language.
  • This is due to an issue with the Russian language file used within PM55xx.
  • This issue is noticed with Pm55xx with firmware versions below 4.1.3


Solution :

  • This issue is fixed in Firmware version 4.1.3 onwards. So the meter needs to be upgraded to this Firmware version.

施耐德電機Taiwan

附件
SchneiderElectric_KBA_Basic_Meter_PM55xx_Russian_language_Issue.pdf [347.55 KB]
探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings