我们今天能为您提供什么帮助?

What are the materials use in the production of the resistive touchpad for HMIDT542, HMIDT642 and HMIDT732 panels?

Issue:
Customer need to know what are the materials use in the production of the resistive touchpad for the HMIDT542, HMIDT642 and HMIDT732 panels.

Product Line:
HMIGTU, HMIDT

Resolution:
The materials use in the production of the resistive touchpad for HMIDT542, HMIDT642 and HMIDT732 panels are: ITO film: Polyester, ITO Glass: Glass, FPC: Polyimide.




If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)

施耐德電機Taiwan

探索更多
產品:
探索更多
產品:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings