Is it possible to supply a Tri phases EVlink Pro AC in Single phase ?
For EVlink Pro AC with embedded RCD, as it is not possible because the RCD manual test won't work .
For EVlink Pro AC without embedded RCD it is possible, you need to set Single phase in eSetup configuration.