For how long does the Bluetooth connection for eSetup remain open on EVlink Pro AC ?

Article available in these languages:

  • Czech

1) If no admin badge is recorded on the charging station, you can activate the Bluetooth connection by powering the charging station Off and then On, and waiting for the strip LED to turn green. The bluetooth will be activated for commissioning and the session will close after 2 hours of inactivity.
2) If an admin badge is recorded on the charging station, tap the admin badge on the RFID reader. The Bluetooth connection will be activated and the session will close after for 10 minutes of inactivity.