Ecostruxure Machine Scada Expert - Display trend Date and Time at the cursor position.

Issue:
How can we display the Date and Time at the cursor position on the Trend object?

Product Line:
EcoStruxure Machine SCADA Expert (all versions)

Resolution:
The date and time at the cursor position is not directly available on the trend graphic. In order to display it, some elements must be configured.

1- Create a global "String" tag that will receive the date and time:

Project Explorer - Global tab - right click on "Tag List" to insert a tag.

In the window, enter the name of the tag and select "String" as the type.

2- Double click on the "Trend Control Object" to open the properties window.

Click on the "Axes" button.

Then the "Cursor" button in the new window.

Enter the tag name in the "Value Output" field.

3- On the graphic page, add a text object to display the date and time.

Go into the "Draw" menu, select the "Text" tool and add a text field.

Define the properties of text field, then click the "Text data link" button.

In the "Tag/Expression", enter the tag name.

Save the modifications.

Test, the date and time at the cursor position should display.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)

施耐德電機Taiwan

附件
Test_Trend.zip [304.62 KB]
探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings