我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
How to read the last Event inside an IED device (IEC61850) buffer report from a BMENOP0300 after an M580 swap?
Context:
In some architecture IEC61850 where M580 HSBY and BMENOP0300 are used, BMENOP0300 is used as client function and communicate with IED device (Protection Relay for example) by using Buffer report.
The buffer report inside the IED device is read by the BMENOP0300.
When using Report Functions, it is recommended to automatically enable the report function for buffered and unbuffered report control blocks by setting the “AutoEna” field to 1 (auto enable). After switchover, the BMENOP0300 module will automatically enables the report when establishing a connection with the remote IED.

IEC61850 configuration device ddt

However, by using Buffer report, during a switchover, the new primary rack will enable the report and read all the events contain in the IED device buffer. For example, inside the IED buffer if there are 50 events, the NOP will read all those 50 events and will make a change from 0 – 1 – 0 – 1 …. 50 times.

Therefore, when using buffer report in a M580 HSBY, we recommend to not set the “AutoEna” field to 1 and to follow the step below in order to read the last event entry inside the buffer (by using the EntryID attribute) before enabling the report:

Auto Enable should be always at 0
IEC61850 configuration device ddt

After a Swap, the report will not be enable. The following step need to be performed and automatize :
Check Health bit with IED

IEC61850 configuration device ddt

Need to read EntryIDs with option “108”

IEC61850 configuration device ddt

Give a Trigger on the “cmd”
You can see that the IED device replied with the number of EntryIDs
IEC61850 configuration device ddt

Write EntryIDs with option “8” to the IED Device
IEC61850 configuration device ddt

Give a Trigger on the “cmd”
IEC61850 configuration device ddt
You can see that the “write” has been well sent because the Report Status give “OK”

Form this point we can proceed to enable report :
Make sure attribute is “1”
Enable Report with option “1”
IEC61850 configuration device ddt

Give a Trigger on the “cmd”
IEC61850 configuration device ddt

At this point, the BMENOP0300 has received only the last event from the buffer of the IED device and report is enable.


Product line
BMENOP0300, M580 HSBY

Environment
Windows, IED device, buffer report

施耐德電機Taiwan

How to read the last Event inside an IED device (IEC61850) buffer report from a BMENOP0300 after an M580 swap?
Context:
In some architecture IEC61850 where M580 HSBY and BMENOP0300 are used, BMENOP0300 is used as client function and communicate with IED device (Protection Relay for example) by using Buffer report.
The buffer report inside the IED device is read by the BMENOP0300.
When using Report Functions, it is recommended to automatically enable the report function for buffered and unbuffered report control blocks by setting the “AutoEna” field to 1 (auto enable). After switchover, the BMENOP0300 module will automatically enables the report when establishing a connection with the remote IED.

IEC61850 configuration device ddt

However, by using Buffer report, during a switchover, the new primary rack will enable the report and read all the events contain in the IED device buffer. For example, inside the IED buffer if there are 50 events, the NOP will read all those 50 events and will make a change from 0 – 1 – 0 – 1 …. 50 times.

Therefore, when using buffer report in a M580 HSBY, we recommend to not set the “AutoEna” field to 1 and to follow the step below in order to read the last event entry inside the buffer (by using the EntryID attribute) before enabling the report:

Auto Enable should be always at 0
IEC61850 configuration device ddt

After a Swap, the report will not be enable. The following step need to be performed and automatize :
Check Health bit with IED

IEC61850 configuration device ddt

Need to read EntryIDs with option “108”

IEC61850 configuration device ddt

Give a Trigger on the “cmd”
You can see that the IED device replied with the number of EntryIDs
IEC61850 configuration device ddt

Write EntryIDs with option “8” to the IED Device
IEC61850 configuration device ddt

Give a Trigger on the “cmd”
IEC61850 configuration device ddt
You can see that the “write” has been well sent because the Report Status give “OK”

Form this point we can proceed to enable report :
Make sure attribute is “1”
Enable Report with option “1”
IEC61850 configuration device ddt

Give a Trigger on the “cmd”
IEC61850 configuration device ddt

At this point, the BMENOP0300 has received only the last event from the buffer of the IED device and report is enable.


Product line
BMENOP0300, M580 HSBY

Environment
Windows, IED device, buffer report
 

施耐德電機Taiwan

探索更多
產品:
探索更多
產品:
探索更多
產品:
探索更多
產品:

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.