我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
How to reset the Geo SCADA super-user account in case you forgot the password
It is possible to reset the Geo SCADA super-user account in case its password is lost. The user must have Windows Administrative rights to that computer.
The procedure is the following:
  1. Shutdown the Geo SCADA Server, wait until it is down, with the Server icon in gray color
  2. Go to Windows Control Panel and select the “Programs and Features” option:
Programs
  1. Under “Uninstall or change a program”,  click on “Schneider Electric EcoStruxure Geo SCADA Expert 2020” (or the version you have installed) and select the “Change” option:
Change
  1. This will bring the Geo SCADA installation splash screen. Click on “Next”:
Splash
  1. Click on “Modify”:
Modify
  1. Check the “Change Super-User Account” check-box (don’t change anything else) and click on “Next”:
Checkbox
  1. Enter the super-user "User Name" and password, then click on “Next”:
user
  1. Click on “Install”:
install
  1. Click on “Finish”:
finish

  1. Now you can start Geo SCADA Server. The new account will be available for use. Note that the super-user account must be used carefully and should not be of public knowledge. Best practice is to disable it when an application has proper security settings in place.

施耐德電機Taiwan

探索更多
產品:
探索更多
產品:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings