Error message "Unable to authenticate the cloud services" in EPC
In EcoStruxure Power Commission, sometimes while generating the QR code you might get error message "Unable to authenticate the cloud services. Please contact CCC to report the issue" as given in screen shot below:

Unable to authenticate


When you face such issues, you can follow the below steps to ensure you are not blocked. You need to make a parameter "false" in the configuration file as mentioned in below steps.

Steps to unblock:

1) Save all your projects and Close EPC (Very important step)
2) Check and confirm whether DigiCert Global Root CA certificate is available in the system. For that please follow below steps:
  1. Press Windows+R  -> Then type certmgr.msc and click on OK
  2. Certificate manager console will be opening and check whether the certificate is installed as mentioned in the below screenshot:
Certificate

If you do not have certificate, please contact Schneider Electric Country Customer Care team
If you have the above certificate please follow the next steps to recover from the error.


3) Navigate to path:
C:\Program Files (x86)\Schneider Electric\Ecoreach V2\Package\Server
4) Find the file "EcoreachCore.exe.config"
5) Right click on this file and click "Edit" with notepad or notepad++
6) Change the following data(by default it will be "true", we are changing to false) :
<add key="ValidateCertificate" value="false" />
7) Save the file and close the file
8) Relaunch EPC application and try to generate QR code

These above steps should unblock you and if you still face any issues, please contact your country customer support team.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings