我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Ecostruxure Automation Expert[22.0]: How to resolve OPCUA communication issue with Aveva System Platform for large projects.
This document explains user on How to resolve OPCUA communication issue with Aveva System Platform for large projects.

By default, the Automation expert keeps some default values related to OPCUA server settings which are given below.

OPCUA3

When User compiles the project, software will automatically checks and gives warning messages to user as shown below.

08-05-18:51:21.935019 WARNING: OPCUA.OPCUAServer: The current number of OPCUA references ( 11965 ) is above the maximum number of OPCUA references supported by the device ( 1000 ).
2022-08-05-18:51:21.935239 WARNING: OPCUA.OPCUAServer: The current number of OPCUA variables ( 5226 ) is above the maximum number of OPCUA variables supported by the device ( 500 ).

Note: The default values has been increased in the latest version from 1000 to 65535 for references and 500 to 25000 for variables.
opcua1

In this situation, the name space "EcostruxureSystemExpert" will not be created in SMC. Thus the OPCUA communication with ASP will not be successful.

opcua2

For resolving this issue, User has to increase the current device settings for "Max. number of Variables" & Max. number of references", more than the values shown in the warnings and then deploy the Device configuration to the Device and Reboot.

After that, User can able to get the "EcostruxureSystemExpert" name space in SMC and the OPCUA communication shall be successful. Some times it was observed that, User needs to to reconfigure the SMC OPCUA configuration for successful OPCUA communication.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings