我们今天能为您提供什么帮助?

How to Point to a Particular Table Name in Historic Data


Using CDBPoint and CDBHistoric.
The CDBPoint tables has several columns that explains the time, date, description, name, and other information about the current state of the data. However, if looking at historic tables, it provides data related to enabled historic data without telling what the name of the point is. As a result, to point to a particular table name in historic data, you need to CROSS JOIN CDBPoint and CDBHistoric.

The Overview
This overview is meant to provide how to point to a particular table name in historic data.
Overview
This is an example:
-In ViewX, create a group and a point or use existing point (right-click design area and click on Edit Query to view  code).
-Click Default Mimic to display design area
-In Graphic, create a LIST and paste the code below:



CDBPoint
The SQL code:

SELECT TOP( 100000 )
"RecordId", "RecordTime" AS "~Time", "FormattedValue", "StateDesc", "QualityDesc", "ReasonDesc", "StatusDesc", "SuppressionTypeDesc", "Foreground", "Background", "Blink", "FileOffset" AS "_FileOffset"
FROM
CDBHISTORIC
WHERE
"Id" = 7051 AND "~Time" BETWEEN { OPC 'Hour - 23 Hours' } AND { OPC 'Hour - 23 Hours+1 Day' }
ORDER BY
"~Time" DESC, "_FileOffset" DESC

CDBPoint

CROSS JOIN CDBPoint and CDBHistoric

You need to modify the code according to the column you would like to view from CDBPoint before you can generate the CDBHistoric table.

-CDBHistoric
-The SQL code:

SELECT TOP( 100000 )
H."RecordTime", P."Name", H."FormattedValue"
FROM
CDBPOINT AS P CROSS JOIN CDBHISTORIC AS H
WHERE
P.ID = 7051 AND H."RecordTime" BETWEEN { OPC 'Hour - 23 Hours' } AND { OPC 'Hour - 23 Hours+1 Day' } AND H.ID = P.ID

CDBHistoric


施耐德電機Taiwan

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings