P3 IEC61850 LN value update failure
Issue
After IEC61850 configuration in P3 relay, customer found that some LN was not updating the actual value.

_____________________________________________________________
Product Line
Easergy P3 relay
_____________________________________________________________
Environment
All firmware version
_____________________________________________________________ Root Cause
Customer didn’t enable the “Event ON/OFF” which is related to the LN, so the change in value is not updated to LN.


_____________________________________________________________
Solution
1- If our customer want to use some LNs in P3 relay, especially for GGIO LNs, customer should enable separate “Event ON/OFF” function as shown below.
2- It will be updated to the manual in future release.
_____________________________________________________________
=====End of document=====
After IEC61850 configuration in P3 relay, customer found that some LN was not updating the actual value.
_____________________________________________________________
Product Line
Easergy P3 relay
_____________________________________________________________
Environment
All firmware version
_____________________________________________________________ Root Cause
Customer didn’t enable the “Event ON/OFF” which is related to the LN, so the change in value is not updated to LN.
_____________________________________________________________
Solution
1- If our customer want to use some LNs in P3 relay, especially for GGIO LNs, customer should enable separate “Event ON/OFF” function as shown below.
| Item | LN(example) | Event ON/OFF |
| Digital input | ||
| Logical output | ||
| Protection | ||
| Virtual input |
2- It will be updated to the manual in future release.
_____________________________________________________________
=====End of document=====