我们今天能为您提供什么帮助?

Why is the estimated runtime displayed on my Smart-UPS LCD not accurate?

Article available in these languages:

  • 法文

Issue: The estimated runtime remaining displayed on the UPS LCD is not accurate

Product Line: Smart-UPS SMC, SMT, SMX and SRT models

Cause: In some cases, the UPS may display inaccurate runtime if the connected load is very low compared to the UPS power capacity. The UPS firmware calculates and displays the estimated runtime based on the connected load and on the actual runtime during the last outage or discharge. The higher the load connected, the more accurate the displayed runtime information will be.

Resolution: For a more accurate runtime estimation, it is recommended to have at least 10% load connected to UPS units that have no external battery backs connected.

Note: If the UPS displays an estimated runtime that is shorter than expected while under very low load, the actual runtime may be longer than the estimated runtime, as the actual runtime depends on the physical power available from the battery during the actual outage.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings