我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Unable to access ATS web interface via HTTPS

Article available in these languages: 法文

Problem:
Users are not able to access the HTTPS web interface of an AP44xxA Automatic Transfer Switch. May receive warnings of invalid certificates

Environment:
AP44xxA Automatic Transfer Switches with an embedded NMC3

Solution:
The default certificate that is preconfigured on the NMC may have an invalid date, which will prevent users from accessing the HTTPS web interface. Users unable to web can log into the ATS using the provided serial cable, and enable HTTP to web in.

After logging in via HTTP, delete the previous certificate by navigating to Configuration --> Network --> Web --> SSL Certificate, and selecting the "Remove" selection, then click apply.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings