我们今天能为您提供什么帮助?

NetBotz camera pod NBPD0165 occasionally changes to black & white image in well lit room.

Issue:
NetBotz camera pod NBPD0165 occasionally changes to black & white image when in a well lit room.

Product Line:
NetBotz

Environment:
NBPD0165 camera pod

Cause:
The NetBotz 165 camera pod has both day and night capabilities. When in night mode / dark mode, the image changes to black and white.
There are occasions where the image will change to black & white during the day or when in a well lit room.

Resolution:
Please log on to the camera directly.

Find the setting under "IR Function" for "Day/Night Threshold".

Change night to day setting from 7 to 4 as per the following image.

Camera Menu

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings