How to manually check and correct Auxiliaries from older project which are not compatible due to new offer Auxiliary Acti9 and Multi9 evolution in V2.5.XX in EcoStruxure PowerBuild – Rapsody.
Issue: Check and correct the non-compatible auxiliaries from project created in version older than V2.1.x.

Product Line: EcoStruxure Power Build – Rapsody

Resolution:
With the new version V2.5.X of EcoStruxure PowerBuild- Rapsody, as the Auxiliaries Acti9 and Multi9 have evolved, it will cause a compatibility breach in EcoStruxure Power Build Rapsody when working on new version V2.5.X with project created in older version V2.1.X which had OF-SD selected for the following offers:
C120
iC60
iC60 double terminals
Acti9 C60H-DC
iSW NA
iDPN N Vigi
iDPN H Vigi
iDPN N Vigi G type

ACTI9 iC40
ACTI9 iCV40 Feeder
ACTI9 iID40
ACTI9 iIG40
ACTI9 iDT40
ACTI9 iDD40 Head of group
ACTI9 iDD40 Feeder














Step1:
Open the old project SSD file in version V2.5.X by using the option “Open an Existing Project” or “Open a recent Project”.

Step2:
When pop-up for project update appears, choose “No”.


Step3:
From “Electrical Organization” tab, Generate functional Names as shown in below screenshot.




Step4:
Click on Update project button image.png and run the project update and check the box for option “Show only the modified references” to get the list of devices impacted.




Step5:
Export the list or save the screenshot for each impacted switchboard.


Step6:
Go to Product Choice and right click on the impacted devices and choose “Modify” and select the required characteristics.  Modify the impacted devices for all the switchboard.



Note: For project with more number of switchboard and devices with auxiliaries, it may take longer time to validate the devices.

施耐德電機Taiwan

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings