我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Why my application does not build when I import some DFB from another application (older version of Control Expert) with same DDT structure assigned?
Possible Cause:

The DDT structure in the new application might differ from the one in the older application. This can happen when types are automatically generated by DTMs, as DTM evolutions may introduce changes.
Additionally, the DDT structure could include hidden variables, causing Control Expert to detect a mismatch between the types and raise an error.



DDT_DFB,Error

To confirm whether you encounter the same issue:

  1. Export both DDTs in .XSY format (the one generated from the new DFB and the one already present in the application).
  2. Open the exported files in Notepad and compare the variable types and names to ensure they are identical.

Example:

DFB,Hidden variable,DDT

If the comparison shows differences:
Update the DDT type used in the DFB so that it matches the one already defined in the application.

Recommendation:
Avoid using DDTs that are automatically generated by DTMs within a DFB, as these can lead to inconsistencies due to DTM evolutions.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings