我们今天能为您提供什么帮助?

How do I upgrade the firmware of the BMENUA0100 OPCUA server module?

First log into the module via the web pages and go to the cyber security setup tab then select access control

image1

Create an account and select the appropriate roles for the user, "installer" necessary

image2

Apply the changes

image3

Launch the Automation Device Maintenance utility and select settings then package settings. The package location is where you copy the firmware file to

image5

The firmware should be available in the list under the data package

image6

Next, select Device/Loading tab and select Add

image7

Set the connection to HTTP/HTTPS and enter the IP address of the BMENUA0100 module then select ok

image8

Device should appear in the device list, make sure the data package reflect the firmware version you are upgrading to. Then select "Device Login" icon and enter the user credential of the module and select "connect"

image8b

The device login icon should turn green indicating a valid login. Next select the "Update Firmware" button at the bottom

image9

施耐德電機Taiwan

探索更多
產品:
探索更多
產品:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings