我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
PowerChute Network Shutdown v5 reports "Could not connect to Host over the network."

Article available in these languages: 日文

Issue:
PowerChute Network Shutdown v5 reports "Could not connect to Host over the network." when configuring with VMware ESXi 8 host.

Could not connect to Host

Product:
PowerChute Network Shutdown version 5

Environment:
VMware ESXi 7 or 8 host that VMware vCenter Server does not manage.

Cause:
Security certificate created with the CN= localhost.localdomain
During the installation of ESXi, the installer generates a self-signed certificate for each ESXi host, but the process is performed before the ESXi identity is configured. This means all ESXi hosts have a common name in their self-signed certificate of localhost.localdomain.



Security Certificate
Solution:
1 - Verify that the ESXi host IP address and/or domain name have been entered correctly.
2 - Verify the ESXi host can be pinged from the PowerChute VM or server PowerChute is running on.
3 - Review the security certificate presented by the host. It should contain the host IP address or domain name as the CN.

If the CN = localhost.localdomain, create a new security certificate after adding the correct domain name to the host.


Option 1: Regenerating ESXi Self-Signed Certificates Using Built-In Tools

1 - Login to the ESXi host over SSH
a. Requires ESXi shell and SSH access to be enabled on the host

2 - Back up the existing certificate files

a. mv /etc/vmware/ssl/rui.crt /etc/vmware/ssl/rui.crt.old
b. mv /etc/vmware/ssl/rui.key /etc/vmware/ssl/rui.key.old
3 - Generate a new certificate that contains the FQDN for the CN value.
a. /sbin/generate-certificates
4 - Restart the hostd service on the host
a. /etc/init.d/hostd restart

5 - Login to the PowerChute VM
a. Edit /etc/hosts file and add the IP address and hostname of the ESXi host
Examples: 192.168.0.100 ESXiHost100.homelab.local or 192.168.0.100 ESXi100 if DNS is not configured.
For help with editing the hosts file, please see How to edit the hosts file on the system PowerChute Network Shutdown has been installed on to.

6 - Reboot the PowerChute VM
a. The command is init 6

7 - Login to the PowerChute web interface
a. Run the setup wizard

Option 2: Manual SSL Certificate Creation and Installation via OpenSSL

1 -  Connect to the ESXi host via SSH and run the following commands to backup existing certificates
  • mkdir /etc/vmware/ssl/bak
  • mv /etc/vmware/ssl/rui.* /etc/vmware/ssl/bak/

2 - Using a text editor (e.g. notepad) and WinSCP, create a custom OpenSSL config file (webclient.cnf) with the following content and upload it in the /etc/vmware/ssl/ folder.

[ req ]
default_bits = 2048
default_keyfile = rui.key
distinguished_name = req_distinguished_name
encrypt_key = no
prompt = no
string_mask = nombstr
req_extensions = v3_req[ v3_req ]
basicConstraints = CA:FALSE
keyUsage = digitalSignature, keyEncipherment, dataEncipherment
extendedKeyUsage = serverAuth, clientAuth
subjectAltName = DNS:esxi.local, IP:192.168.1.100[ req_distinguished_name ]
countryName = PH
stateOrProvinceName = Cavite
localityName = Cavite
organizationName = YourCompany
organizationalUnitName = IT
commonName = esxi.local
3. Run the following commands on the ESXi host to generate a new key, CSR and SSL certificate:
  • openssl genrsa -out /etc/vmware/ssl/rui.key 2048
  • openssl req -new -nodes -out /etc/vmware/ssl/rui.csr -keyout /etc/vmware/ssl/rui.key -config /etc/vmware/ssl/webclient.cnf
  • openssl x509 -req -days 365 -in /etc/vmware/ssl/rui.csr -signkey /etc/vmware/ssl/rui.key -out /etc/vmware/ssl/rui.crt -extensions v3_req -extfile /etc/vmware/ssl/webclient.cnf

4. Restart the ESXi host services to apply the new certificate

/etc/init.d/hostd restart && /etc/init.d/rhttpproxy restart

Note: In certain cases, the steps outlined above may not successfully apply the updated SSL certificate. If the changes do not take effect, performing a full system restart of the ESXi host may be necessary to ensure the new certificate is properly loaded and recognized.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings