Is the embedded NMC capable of reading or detecting the AP9613 dry contact when inserted into the Smart slot of the UPS?
Issue: Clarification about the accessory board (AP9613) and the embedded NMC
Product line: All Smart UPS with Embedded NMC and available Smart slot
Answer:
No! The embedded NMC cannot detect or read the dry contact AP9613.
An embedded NMC as well as the removable/preinstalled NMC can only detect a dry contact which is directly connected to its I/O port.
Product line: All Smart UPS with Embedded NMC and available Smart slot
Answer:
No! The embedded NMC cannot detect or read the dry contact AP9613.
An embedded NMC as well as the removable/preinstalled NMC can only detect a dry contact which is directly connected to its I/O port.