我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
How to troubleshoot outlets not working on a switched rPDU
Issue:
When powering on a switched rack PDU, one or more groups of outlets are not supplying power

Product:
APC Switched rPDU's, including but not limited to AP79xx, AP86xx, AP89xx, APDU99xx, APDU10xx models

Solution:
There are a few causes for groups of outlets to remain off on a switched rPDU. If a user finds some or all outlets not supplying power, please check the following:

- rPDU bank breakers: rPDU's 30A and above have circuit breakers to protect the individual banks. Confirm that the breakers have not been tripped, and remain in the "off" position. For information on how to reset breakers, please see FA156088

- rPDU outlet LED: Switched rPDU's have green LED's near each outlet, which when lit show that the outlet is currently enabled and supplying power. If the rPDU outlet LED is off, then the outlet may have been commanded off by a user.

- rPDU web interface: Switched rPDU's use a network interface for user control of individual outlets. It is possible to enable/disable outlets, as well as control outlet turn-on order and timing when power is applied to the rPDU. It's possible certain outlets have been configured or commanded to remain off, and need to be enabled again through the network card. Please see the relevant user guide for each specific rPDU for more information on where outlet control exists within the user interface. Retrieving the event/data/config files can also help confirm if there is a configuration issue, or other fault present.

- rPDU outlet measurements: If a user has a multimeter/voltmeter handy, they can manually check the voltage present at the outlet by retrieving measurements between Line, Ground, and Neutral/Line2 to confirm they are valid.


If a user has gone through the above and power is still not present at the outlets, please contact the APC support team.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings