我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
ATV340 tripping on Internal Error 22 or INFM

Issue:

What can cause [Internal Error 22] InFM?

Product Line:

ATV340

Environment:

All

Cause:

An error on the embedded Ethernet card has been detected.

Damaged embedded ethernet card

Instability of the 24Vdc supply

Resolution:

This is due to Ethernet crash.

Also, if ATV340 is supplied only to external 24V and 24V used is not stable, the drive may trip on INFM.

Remedies:

Verify the connection on the Ethernet port.

Verify the 24Vdc supply stability.

INFM can be mitigated by:

Using separate, good quality external 24V dc power supply, exclusively dedicated for control blocks (no other devices supplied from it).

Improve EMC for 24V dc wiring (shielding, proper distance from power cables).

Important to check (drive grounding, Eth cables shielding/grounding, other EMC rules).

Update drive firmware if it is older.

This detected error requires a power reset.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings