PAS800 csv export missing data for A9MEM1540/A9MEM1520 wireless sensors
Issue
PAS800 csv export missing data for A9MEM1540/A9MEM1520 wireless sensors
Product Line
PAS800
A9MEM1540/A9MEM1520
Environment
PAS800 FW1.6.0/FW1.x.x
A9MEM1540/A9MEM1520 FW 1.x.x
Cause
Minimum firmware requirement for A9MEM1540/A9MEM1520 wireless devices to be supported by PAS is v4.0.424.
Resolution
Need to use the wireless devices with minimum firmware listed in the device support matrices mentioned in PAS800 Firmware release notes.

For PAS 800:
https://www.productinfo.schneider-electric.com/ecostruxurepanelserveradvancedrn/doca0248-ecostruxure-pas800-release-notes/English/DOCA0248 EcoStruxure Panel Server Advanced Release Notes _0000901901.xml/$/RN_EcoStruxurePanelServerPAS800_Wireless_Devices_0000908226
For PAS 600:
https://www.productinfo.schneider-electric.com/ecostruxurepanelserverrn/doca0178-ecostruxure-panel-server-release-notes/English/DOCA0178 EcoStruxure Panel Server Release Notes_0000632581.xml/$/RN_EcoStruxurePanelServerRN_Wireless_Devices_0000632789
Note
PAS800 csv export missing data for A9MEM1540/A9MEM1520 wireless sensors
Product Line
PAS800
A9MEM1540/A9MEM1520
Environment
PAS800 FW1.6.0/FW1.x.x
A9MEM1540/A9MEM1520 FW 1.x.x
Cause
Minimum firmware requirement for A9MEM1540/A9MEM1520 wireless devices to be supported by PAS is v4.0.424.
Resolution
Need to use the wireless devices with minimum firmware listed in the device support matrices mentioned in PAS800 Firmware release notes.
For PAS 800:
https://www.productinfo.schneider-electric.com/ecostruxurepanelserveradvancedrn/doca0248-ecostruxure-pas800-release-notes/English/DOCA0248 EcoStruxure Panel Server Advanced Release Notes _0000901901.xml/$/RN_EcoStruxurePanelServerPAS800_Wireless_Devices_0000908226
For PAS 600:
https://www.productinfo.schneider-electric.com/ecostruxurepanelserverrn/doca0178-ecostruxure-panel-server-release-notes/English/DOCA0178 EcoStruxure Panel Server Release Notes_0000632581.xml/$/RN_EcoStruxurePanelServerRN_Wireless_Devices_0000632789
Note
- For EEH data publication please refer EEH solution supported architecture. https://ecostruxure-energy-one.se.app/relay/cdn/help/en-us/Content/G-Other-Topics/O-Reference/SupportedDevices-List.htm?Highlight=PM8000,
發佈於: 施耐德電機Taiwan

