我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
What should customer do when the diagnosis LED flashes during the Giga contactor in normal operation?
After customer changes the switching modules on the Giga contactor, customer should reset the contactor by changing the dip switch from “A” to “B” OR from “B” to “A”.
Before the date code 2335(Year 2023, Week 35) of the Giga contactor, Schneider puts the dip switch in the A position during the manufacture.
After the date code of 2335, Schneider decides to move the position to B during the manufacture.
Before the date code 2335(Year 2023, Week 35) of the Giga contactor, if customer observes the diagnosis LED flashing on the front face of the Giga contactor during the normal operation, customer can try to move the dip switch from “A” to “B” and keep the dip switch in B position.
Below extracted picture shows how the LED light flash from the user manual DOCA0189EN page 18:

image001

After the dip switch is in B position, customer can power on A1 and A2 of the contactor. the diagnosis LED is blinking, and the contactor remains open. It closes after 10 seconds.
Then, the diagnosis LED will be off, and the contactor can work normally.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings