我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
How to bit-pack 16 bits into a SCADAPack x70 analog object associated with a Modbus holding register

When using SCADAPack x70 devices, it may be desirable to pack 16 bits into a Modbus holding register. This is typically wanted when the SCADAPack is acting as a Modbus Server. When using RemoteConnect, all protocol facing values need to be in “objects” in the SCADAPack database.

Logic:
If you need to pack 16 bits into a Modbus holding register, a user will create an object associated with a Modbus address. The Logic Variable Type will be “T_SPx70_UINT”.
In the logic editor, the user will use a combination of “BIT_TO_WORD” and “WORD_TO_UINT” function blocks. The inputs to the “BIT_TO_WORD” block can be a combination of Elementary variables and Derived variables that are part of the x70 object database.

Below are visual examples of the objects and logic needed to bit-pack an object with up to 16 bits. The 16 bits will be available in Modbus register 40001 (object ModbusBitPack). Any SCADA/RTU/PLC client can poll for Modbus register 40001 and get the bit-packed value.

Object List

Logic Example

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings