How to force return PME license version >2021 (license configuration tool)

Issue

A license may become unreturnable through use of the License Configuration Tool

Some situations may include a customer's PME server crashing or migrating, causing the license to become untrusted on the customer's machine, but remain activated in the Schneider Electric servers

NOTE: Starting from PME 2021 and going forward, the License Configuration Tool is used for license configuration and has a different process to force return licenses than the Floating License Manager.



Product Line

Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Power Monitoring Expert 2024



Environment

License Configuration Manager



Cause

When a license is activated using the online method and later taken offline, it cannot be returned with the conventional online methods.

If the license has been activated using the online method, but the server no longer has internet access. The following method will release the license.

Resolution

A license can be force returned by following the steps below:

1) Email your local Schneider Electric support group with the relevant Activation ID and request that it be manually released
2) After receiving confirmation that the licenses have been released, follow the next steps:
3) Close the License Configuration Tool, as well as any Power Monitoring Expert applications that may be open
4) Open File Explorer and confirm Show Hidden Items is checked:

image
​​​​​5) Use the above screenshot to verify that the "ProgramData" folder is visible, then navigate to "C:\ProgramData\Schneider Electric\Power Monitoring Expert\License"
6) Delete all the hidden files in this "License" folder
7) Relaunch the License Configuration tool
8) Activate the license using the offline method

施耐德電機Taiwan

探索更多
產品:
探索更多
產品:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings