How to set properties and retrieve logs from GSE acting as an OPC UA Server
The feature that allows GSE (Geo SCADA Expert) to work as an OPC UA Server is new to the product (in GSE 2022) and uses a different approach when compared to GSE working as an OPC DA Server. When there is a need to troubleshoot GSE as an OPC DA Server, the DB log files are the ones to be analyzed. GSE as an OPC UA Server is different, it relies on AVEVA PCS Service and a particular driver was developed to manage it.
When it is necessary to troubleshoot GSE as an OPC UA Server, logs from the PCSService are the ones to be retrieved and sent to Technical Support.
The settings for the PCSService driver can be found by going to the Server Status tool > General > Modules page:

server status

Right-click on "PCSService" and select "Logging...":

logging


Under "Current Options" tab, select the "I/O" option (background will turn blue), click on the "Make Default" button, click on the "Apply" button:


io

Under "Configuration" tab, the end user can see the location of the log files and adjust the size and number of files to keep:

configuration

location

After performing the tests and retrieving the log files, the end user can disable the I/O flag by going again to the "Current Options" tab, clicking on the "I/O" option (so it will be not selected, in white background), clicking on the "Make Default" option, and then on the "Apply" button:

uncheck io



施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings