我们今天能为您提供什么帮助?

EcoStruxure Process Expert[2023]: Unable to configure the M580 controller after migration?

This knowledge base explains the user about the steps to overcome the issue which he may face when he tries to configure the M580 controller in Ecostruxure Process Expert 2023 version.

After the migration from previous versions to Ecostruxure Process Expert 2023,user tries to configure the M580 controller from topology explorer. If the configuration has BMxNOCxx module, he faces the below issue.

Image-1

Even though the error screen shot shows user that more than one NTP server is enabled however, none is configured as NTP server.

User has to follow the below workaround to overcome the issue. The same has been mentioned in EPE 2023 release notes as well.

In the services tab of the controller properties, click on the enabled checkbox and change the NTP state from NTP client to NTP server, as shown below :

Image-2

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings