我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
EcoStruxure Power Operation (EPO) 2022: Failing to supply license to OFS Factory Server which was installed during EPO 2022 installation

Issue

This is a known issue with the OFS tool supplied along with the EPO v2021/v2022 installer in which it is failing to get licenses from EPO.

Environment

EcoStruxure Power Operation (EPO) 2021 / 2022.

Resolution

This is a known issue with the OFS tool supplied along with the EPO v2021/2022 installer and same has been fixed in the latest version of OFS. Hence it is recommended to uninstall existing version of OFS v3.62 and install the latest version of OFS 3.63 Service Pack 2 available at this link -

OFS Uninstall/Install Procedure:

1>   Go to control panel and uninstall the OFS v3.62.

2>   Download the latest version of OFS v3.63 with SP2 (OFS_V3.63_4904_SP2_L.iso) from this link-https://www.se.com/sg/en/download/document/OFS_3_63_4904_SP2/

3>   Install the OFS v3.63  downloaded at step-2 and use below details during installation

a.     PartNumber "TLXCDOFS"
b.     Serial number "12345678910"

For more information refer below SE exchange community link (v2022 Release & Updates Install Procedure) and we recommend downloading the latest version of installer ISO files available at below link -

https://community.se.com/t5/EcoStruxure-Power-Operation/v2022-Release-amp-Updates-Install-Procedure/m-p/416561/thread-id/6058

Note: This KB Article supersedes the FAQ000243121.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings