ION9000 Data Not Showing on Connected Panel Server
Issue: ION9000 is serially connected to Panel Server. Registers can be read on the panel server and through Modscan but data is not populating on the panel server webpage.
Product Line:
ION9000
EcoStruxure Panel Server - Advanced
EcoStruxure Panel Server - Universal
Environment:
Panel Server Webpage
Cause: The Panel Server does not have a native device file for the ION9000.
Resolution:
A custom device file will have to be created in order to see data. This can be done in EcoStruxure Power Commission. Reference:
Custom Models for Downstream Modbus Devices (Universal and Advanced Models)