我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Upload error “An item with the same key already exists…”

Issue

On a site where the data is uploaded via history file (not via cloud connection), an upload error occurs in Power Advisor “An item with the same key already exists…”

Cause
This error is usually a result of device duplication in historical data.


UploadError_DuplicateDevices
Resolution

If this error arises, initiate a discussion with the customer about the possibility of discarding the historical record and starting fresh.

If the customer consents, you can  'clear site' to restart the site as new as a workaround.

  • Power Advisor > Hierarchy tab > “Clear Site” option added to Save As dropdown

    A “Clear Site” option has been added to the Save As dropdown located on the Hierarchy tab. Selecting the “Clear Site” option will allow users to clear a site’s metadata.

    As a precaution, after selecting the “Clear Site” option, the user is prompted with a warning that the clearing action will result in lost information. The user must also type the name of the customer site into a text box to confirm the clearing of the site.

    Note that site settings will be retained.

    The “Clear Site” operation is audited for tracking who took the clearing action and when.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings