我们今天能为您提供什么帮助?

Is it possible to have a specific K1/K2 camswitch IP65 ?

Article available in these languages:

  • 法文

The standard delivery is IP40 for K1/K2

Witrh configurator, it is possible to select a gasket (KZ73) in accessories but only for multifixing operating heads with 45X45 front plate (you need to select a label)

For front mounting, the configurator software doesn't propose IP accessories

--> For front plate 45X45, as the reference KZ65 is canceled, I suggest to order it through generic reference GCR_K1S + technical text KZ65

--> For front plate 60X60, the reference KZ66 is still commercialized. It can be ordered separately.

施耐德電機Taiwan

探索更多
產品:
探索更多
產品:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings