我们今天能为您提供什么帮助?

What does 'Demand State' mean in an M580 safety application?

The demand state refers to the condition when a safety function must act to bring a process to a safe state such as when a hazardous event or fault occurs.

In this state, the process moves from normal operation (no demand) to performing its safety action, such as de-energizing outputs, shutting down motion, or cutting power (demand).

The demand state can be either energized or de-energized, depending on how the process is designed to reach its safe condition:

  • De-energize to trip: The system becomes safe when power is removed (e.g., closing a filling valve to prevent tank overflow or stopping gas injection during a leak).

  • Energize to trip: The system requires energy to achieve safety (e.g., energizing a valve to release fire suppression water).

While the PLC safe state is always de-energized, the process demand state may differ. Ideally, both should align, but this isn’t always possible depending on the application design.

For information regarding demand states and different application used, please reference the Modicon M580, Safety Manual | Schneider Electric.

施耐德電機Taiwan

探索更多
產品:
探索更多
產品:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings