我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Power Monitoring Expert (PME) Management console error shows "Invalid column name 'SecureConnectionEnabled'. Invalid Column name 'CertificateValidation'." after a reconfigure. Windows Services fail to start.
Issue
After running a "reconfigure" on PME 2022, an error appears in the management console application:
Management Console error message showing "Invalid column name
In addition, the PME Windows Services will not start.

Product line
Power Monitoring Expert 2022

Environment
PME Management Console
Windows Services

Cause
After running a reconfigure from the PME 2022 installer (.iso) on a system with a PME 2022 Cumulative Update (CU) already installed, a reconfigure needs to be run on the CU as well. This is noted in the PME 2022 CU1 Release Notes:

PME 2022 CU1 Release Notes Note. "Using PME 2022 ISO, if user performs Reconfigure, Reset Accounts, Export System Key, Import System Key on a system where PME 2022 CU is already installed, the step "Start Service" and "Verify registered Services" may show as failed. We recommend continuing with further installation by clicking "Try Again" to continue with the installation. As a mandatory next step, we recommend running PME 2022 CU reconfigure using PME 2022 CU.exe on top of it before using system for any further use."

Resolution
  1. Locate the PME Cumulative Update (CU) installer and run as an administrator.
  2. Select "reconfigure."
  3. Allow the installer to run through the reconfigure steps.

施耐德電機Taiwan

附件
PME 2022 CU1 Release Notes.pdf [2.59 MB]
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings