Can PowerChute Network Shutdown restart the Computer/Server?
Issue:
How does the operating system restart when AC has been restored?

Product:
PowerChute Network Shutdown


Environment:
All supported operating systems

Cause:
Computer/Server restart automatically required

Solution:
PowerChute is software running on a computer or server. When the system is powered off, PowerChute is no longer available and, therefore, cannot restart the system. This is the same as if the user wants to create a text document. If the system is powered off, the text editor cannot run.

The system BIOS is responsible for automatically starting the system. Many systems available today use the ATX motherboard, which supports a soft switch to turn the system On and Off. The implementation of this soft switch includes a BIOS parameter, which defines the state the computer will enter when the power supply senses input power when plugged into the wall. This BIOS parameter can have any one of three values :

ALWAYS ON: When power is cycled, the system automatically turns on and boots up.

ALWAYS OFF: When the power is cycled on, the system stays off until the user manually hits the On/Off soft switch.

LAST STATE: When power is cycled on, the system will either come on or stay off, depending on whether it was on or off when the power was lost.

Most computer/server manufacturers set this parameter to Last State, and some set it to Always Off. It is improbable to find the Always On parameter setting. In many cases, the computer/server manufacturer permits the user to change the value of this parameter by using the system setup menu, which can be accessed before the operating system loads when the computer/server is turned on.

Our recommendation is to set the BIOS to Always On.

Once the BIOS has been configured to allow the OS to restart, the UPS or outlet group must be told to power off. To power off the UPS or outlet group, configure the UPS shutdown within PowerChute.
UPS Shutdown Settings
If the UPS or outlet group is not commanded off and AC is restored during the shutdown process, the UPS will not cut output, so the BIOS will not restart the system.

NOTE: Some Smart-UPS only allow turning off the UPS, others allow for turning off the UPS or the outlet group, and PowerChute cannot command down some 3-phase UPS.


施耐德電機Taiwan

探索更多
系列:
探索更多
系列:

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings