我们今天能为您提供什么帮助?

PowerTags Upstream Protection

The PowerTags instructions sheet states that the PowerTags must be associated with an easily accessible upstream protection and circuit-breaker system, marked with callout A in the schematic below:

block A

What type of protection (Block A) should be used?

The block A represents a protection (MCB, RCCB, switch) that allows the circuit monitored by PTag to be turned off. In most cases, it’s an existing device in the customer's installation. However, in some specific use cases where it’s very hard to turn off the circuit monitored by PTag (for example, in a data center), it can be useful to power the PTag with a dedicated protection. Any MCB up to the PTag's maximum current can be used, or a switch with an upstream MCB.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings