我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
How to do a correct grounding of TM7 CANopen Bus coupler?

We have to use the recommended mounting plate (TM7ACMP), it connects via both screws to the internal functional EARTH potential, that is used for diverting any interference voltage.

backplate grounding

There is no connection of internal ground (electronic ground e. g. CAN_GND) to EARTH (module backplane or DIN rail).
CAN_SHLD (shielding) is connected to EARTH  (module backplane).
CAN_GND (common internal potential of CAN circuit) is connected to EARTH only by a capacitor and a varistor for EMI reasons.

Pins description of connectors

CAN_GND of master has to be connected to CAN_GND of slave. Will be done by appropriate cable. As well as shieldings will be connected.

internal connections

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings