我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Basic Meters Display Time Mismatch with PME After Time Sync

Issue description:

When the meter is connected to PME, a few minutes after the time sync, the time shown on the meter display does not match the time displayed in PME.

Environment:

PME Management Console, Basic Meter Display Settings

Cause:

PME sends only a UTC time sync request to the device. The time on the meter display changes to UTC time if the device is synced with PME.

Resolution:

To ensure that the time in PME and the device is the same, follow the steps below:

  1. Change the meter time from GMT to local time and provide the correct GMT offset on the meter display.
    (Example: If the time zone is UTC+8, set the offset on the meter display to 8.0.)

Meter Display

  1. Select the correct time zone in the PME Management Console.

Management Console

Once the device is synced with PME, the time on the meter display and the PME device diagram will show the same time.

Note: With these settings, the ION Setup will display only the UTC time for the device.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings