我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
PME2024 TGML Component Binding

Issue Description:
TGML component binding is not working in PME2024.

Environment:
PME Graphic Designer

Cause:
The binding property was changed in PME 2024, which prevents the use of component binding.

Component Binding

Below error will appear in the web application:

Web App Error

Resolution:
Follow these steps to fix the component binding issue:

  1. Navigate to the PME installation folder.
  2. Open app.js from this location: Applications\\SystemDataService\\Content\\Applications\\Diagrams\\Scripts\\TGMLviewer.
  3. Search for bindings[bindFullName] = bindName; in app.js.
  4. Comment out bindings[bindFullName] = bindName;. Workaround
  5. Save app.js.
  6. Perform an IIS reset and refresh the PME web application.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings