How to lift the PrismaSeT I Switchboard

!!!Confidential Content

PrismaSeT I offers a lifting kit which compromises of 4 parts- Cage nuts, Lifting hooks, Screws and Washers. The 4 lifting hooks shall be fastened at the four corners on the roof of the switchboard in the inward direction as in fig 1 and its locations shall be as per the dimension of the lifting section. see fig 2.

lifting arrangement 1

Fig 1

lifting arrangement 2 lifting arrangement 3 lifting arrangement 4 lifting arrangement 5

Fig 2

For Combination of cubicles lifting beam is mandatory. see fig 3 and location of fixation shall be as per Fig 4.

lifting arrangement 6

Fig 3

lifting arrangement 7 lifting arrangement 8

Fig. 4

Important points to note while lifting a switchboard.

1) Incomer shall be lifted separately.

2) Maximum shipping section width shall be 1800mm for outgoing verticals.

3) The acute angle between the lifting chains and horizontal top of the switchgear must never be less than 45°.

4) For Single cubicle, lifting brackets shall be used up to 2500A rating only.

5) If there are more than 2 sections than support angles shall be used between two section to maintain alignment. see. fig 5

lifting arrangement 9

Fig 5

For More information on lifting, please refer to the latest lifting guidelines in TTF.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings