我们今天能为您提供什么帮助?

EcoStruxure Control Expert - Impossible to go in on-line mode / Error 203 message when connecting to PLC from DTM Browser

!!!Confidential Content

Issue

When in the EcoStruxure Control Expert > DTM Browser window, and attempting to Connect to the BMEP58_ECPU_EXT node via EIP Explicit communication, we get the messages:

"Impossible to go in on-line mode."

and "NA_Config Cannot StartDriver (Error 203)"

Error message dialogs

Product Line

EcoStruxure Control Expert

Cause

There are a few common causes:

A) There is a physical break in the ethernet connection

B) The IP Address Subnet of the computer is different than the PLC

C) There is a managed switch or firewall rule blocking the Ethernet/IP TCP port 44818

D) There is a separate application that is running on the computer that is reserving TCP port 44818 for itself

Resolution

Steps to troubleshoot:

For (A) physical break in the ethernet connection and (C) a managed switch or firewall rule blocking the Ethernet/IP TCP port 44818

1) Try a running a new CAT5E cable directly between your laptop/workstation running EcoStruxure Control Expert and the PLC.

2) If it works, inspect your old cable for failure, and/or inspect the settings on your managed switch to ensure passage of TCP and UDP packets on port 44818 to the PLC.

NOTE:

If the network is managed by an IT department, please contact them and tell them you would like to free up the TCP and UDP port 44818 and UDP port 2222 for Ethernet/IP communication.

For (B) IPv4 Subnet of the computer is different than the PLC

1) Go to Control Panel

2) Go to Network and Sharing Center

3) Click on "Change adapter settings"

4) Right-click and go to Properties on the Network you wish to view/edit

5) Click on "Internet Protocol Version 4 (TCP/IPv4)"

6) Change the IP Address to match the subnet of the PLC.

IP Address setting in Windows

7) Hit OK and OK again

8) In the DTM Browser screen, double-click on the PLC node (1st node directly under "Host PC")

9) In the Channel Properties, Source Address section, click on the dropdown next to IP Address Source (PC)

10) Choose the IP Address associated with the Network node of your PC

IP Address Source (PC) dropdown

11) If you needed to change this, hit [Apply] at the bottom corner.

12) Check that it matches the IP Address of the PLC from the Channel Properties > TCP/IP node:

IP Address of PLC

In the case of (D) there is a separate application that is running on the computer that is reserving TCP port 44818 for itself

1) From the Start bar search box, type "Resource Monitor"

2) Run the Windows Resource Monitor

3) Go to the Network Tab

4) Expand Listening Ports

5) Sort by the Port column

6) Find 44818

7) If the Image name is not "ControlExpert.exe", take note of what is the Image and PID of this row, this will be the software which is blocking the port.

Windows Resource Monitor - Listening Ports

For example:

If you have Rockwell Studio 5000 software installed on the same computer.

Even if Rockwell Studio is not running or RSLinx itself is not running, the process "RSLinxNG.exe" running a service called "FactoryTalk Linx OPC Runtime Service" reserves the port 44818.

One will need to stop the service from Windows Services and then ensure that the PID is indeed Terminated:

RSLinxNG.exe service

That will free up the port and allow Control Expert to use it and allow the DTM connection to the M580.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:

需要協助?

需要協助?

產品選型工具

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

支援中心

在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings