Installer package error gets returned when upgrading to a newer CE version by installing it on top of an older version.

Windows saves a copy of the installation files for the 'Microsoft C++ Runtime' libraries and 'Control Expert' under the folder named 'C:\Users\Public\Downloaded Installations'.   Depending on the group policy, it might not have had access rights for saving the files to the folder.  If an installer related error gets returned when trying to install a newer version of 'Control Expert' on top of an older version', the issue could be due to the installer software not being able to find the necessary files required to perform the uninstallation of the older version within that folder.

The following steps can be used to resolve the issue:

  • Mount the iso image for the older 'Control Expert' version.
  • Run 'Setup' as an administrator.
  • Select 'Remove' to uninstall 'Control Expert'.
  • Open the 'Programs and Features' in the 'Control Panel'.
  • Uninstall all the DTM libraries that were installed by the older 'Control Expert' version.
  • Reboot.
  • Mount the iso image for the newer 'Control Expert' version.
  • Run 'Setup' as an administrator.
  • Reboot the PC after the installation completes.
  • Open 'Control Expert' to verify that there are no problems.
  • Close 'Control Expert'.
  • Open the 'Security Editor' and verify that it is working.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings