How do I setup the OFS Server as a service on Windows Server 2022?

Issue:

Running OFS server as a service on Windows Server 2022


Product Line:

OFS server


Resolution:

To run OFS Server as a service follow the steps below...

  1. Install the OFS Server on the PC
  2. Run the ofsservice.bat file located in C:\Program Files (x86)\Schneider Electric\OFS\Server

note: with OFS Server V3.63 SP3, the batch file is not created automatically with the installation of the server. You must create it manually in the

C:\Program Files (x86)\Schneider Electric\OFS\Server directory. To create the batch file, create a new text document and rename it to ofsservice.bat then edit the file and enter the command

"regofsservice /true" in the file and save the file.

image1

3. Check to make sure the service is created as shown below. You can change the startup mode to automatic and start the service

image2

4. The server must be setup in the DCOM configuration. Type in dcomcnfg in the search on the tool bar to enter the DCOM configuration. Look for the Schneider-Aut OPC factory server, right click and select properties image3

5.  Under the general tag, select Connect as the Authentication Level

image4

6. Under the Identity tab select this user and enter the login user credentials then select apply and ok

image5

施耐德電機Taiwan

探索更多
產品:
探索更多
產品:

需要協助?

需要協助?

產品選型工具

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

支援中心

在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings