我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Does the iEM3400 and iEM3500 series meters support High leg Delta wiring?

Issue

Can the iEM3400 and iEM3500 series meters be wired as high leg delta or not?

Product line

iEM3400 and iEM3500

Environment

Application requires the installation of a power meter or replacement existing meter in a high leg delta system.

Resolution

No. These meters (iEM3400 and iEM3500 Series) do not support the electrical system type for High-Leg Delta.

The electrical system types supported, per the User Guide, https://www.se.com/us/en/download/document/7EN02-0438/

3PH3W

3PH4W

1PH2W L-N

1PH2W L-L

1PH3W L-L-N

1PH4W Multi L-N

As an alternative, please look at the PM5000 series for High Leg Delta supported models.  See FAQ FA232893

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings