我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
OFS (OPC Factory Server) Error 1053: The service did not respond to the start or control request in a timely fashion

Issue

Error 1053: the service did not respond to the start or control request in a timely fashion is displayed when attempting to start/restart the OFService.

Service error

Product Line

OFS

OPC Factory Server

Environment

Windows Services

Cause

OFService is failing to start within a specified amount of time

Resolution

  1. In the Windows search bar look up Services, right-click, and run as Administrator
  2. find the service where the error occurred, right-click on it, and Select Properties
  3. In the Properties window, click the Log On tab
  4. Make sure the "This Account" option is selected and enter the username and password for the account with administrator privileges
  5. click the Apply button, then click the OK button
  6. Restart your computer and check if the service has started successfully

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings