我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
How to download event waveforms from an AccuSine

Issue: Waveforms from certain Event Log entries may be required to help technical support troubleshoot the issue.  The following process outlines the steps to download the waveform data to a USB flash drive so it can be analyzed by technical support.

Product Line
AccuSine PCS+
AccuSine PCSn
AccuSine EVC+


Resolution

A USB flash drive will be needed in order to download the waveform data from the AccuSine.

The flash drive needs to be formatted to the FAT32 storage type.  The following steps are provided to format the drive to FAT32 in case it is not already formatted to FAT32.  These instructions are for Windows PC's. If the drive is not formatted to FAT32, it could cause errors to occur when downloading the event log.

Note: Formatting the USB drive will erase all data on the drive.

  1. Connect the drive to your computer.
  2. Open File Explorer and navigate to "This PC".
  3. Right-click on the drive you want to format and select "Format".
  4. Choose "FAT32" from the "File system" dropdown.
  5. Click "Start" to begin the formatting process.

  1. Once the drive has been formatted, insert the USB drive into the USB-A port below the HMI or into one of the USB-A ports on the back of the HMI.
  2. Use the HMI to navigate to the Event Log by selecting the "Event Log" icon from the home menu.

    Home menu

  3. Select the event by touching it on the HMI.  The black dot on the left side of the screen indicates which event is selected.  Once the event is selected, select the Magnifying Glass to display more details of that event.

    Event log
  4. The screen should now look like the screen below.  You will see an icon with a computer and waveforms at the bottom of the screen.  Select this icon.

    Event details
  5. The screen should now look like the image below.   There is a Folder with a downwards facing arrow icon at the bottom of the screen, which saves detailed sample data to the flash drive.  Select the Folder Icon to download waveform data onto the USB flash drive.

    Waveform event scope

  6. Once the waveform data has been downloaded, it can now be sent to technical support for further analysis.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings